Papua New Guinea Plate heat exchanger unit
Product Description

Compact Steam Rapid Heat Exchanger Unit
When most employees turn on the tap at the same time during a specific period, the system must be able to immediately supply hot water at a stable temperature.
In an instant, some employees might turn off the faucets simultaneously, so a constant water temperature is required.
When you first turn on the tap, there’s no need to let a lot of cold water run first.
The water temperature must be safe; hot water that could scald employees is not permitted.
The water must be sanitary; it must not come into direct contact with industrial steam, nor should hot water with a long residence time be used.
Heat exchange equipment should occupy minimal space in the machine room, exhibit low fouling rates, require minimal maintenance, and feature unattended operation with alarm notification capabilities.
| Model number | LZ-50-N- | LZ-200-N- | LZ-300-N- | LZ-450-N- | LZ-1200-N- | LZ-800-N- | |
| Heat Load (kW) | 150 | 200 | 300 | 150 | 600 | 800 | |
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 255.9 | 341.2 | 511.7 | 767.6 | 1023 | 1365 |
| Steam pipeline | 32 | 40 | 50 | 65 | 80 | 80 | |
| Condensate piping | 20 | 20 | 25 | 32 | 80 | 40 | |
| Heat source: 95/70℃ high-temperature water | Traffic | 5.2 | 6.9 | 10.3 | 15.4 | 20.6 | 27.5 |
| Takeover Specifications | 40 | 50 | 50 | 65 | 80 | 80 | |
| Secondary side: Water 10/60℃ | Traffic | 2.6 | 3.4 | 5.2 | 7.7 | 10.3 | 13.8 |
| Takeover Specifications | 32 | 40 | 40 | 50 | 50 | 65 | |
| Overall dimensions | Length * Width * Height | 1700*800*850 | 1700*1000*850 | 1850*1000*920 | 1900*1200*980 | 1900*1200*980 | 2050*1400*1280 |
| Model number | LZ-1000-N- | LZ-1200-N- | LZ-1500-N- | LZ-2000-N- | LZ-2500-N- | LZ-3000-N- | |
| Heat Load (kW) | 1000 | 1200 | 1500 | 2000 | 2500 | 3000 | |
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 1706 | 2047 | 2559 | 3412 | 4265 | 5117 |
| Steam pipeline | 100 | 100 | 100 | 125 | 150 | 150 | |
| Condensate piping | 40 | 50 | 50 | 50 | 65 | 80 | |
| Heat source: 95/70℃ high-temperature water | Traffic | 34.4 | 41.3 | 51.6 | 68.8 | 90.1 | 103.2 |
| Takeover Specifications | 100 | 100 | 125 | 125 | 125 | 150 | |
| Secondary side: Water 10/60℃ | Traffic | 17.2 | 20.6 | 25.8 | 34.4 | 43 | 51.6 |
| Takeover Specifications | 65 | 80 | 80 | 100 | 100 | 100 | |
| Overall dimensions | Length * Width * Height | 2050*1400*1280 | 2100*1500*1280 | 2100*1500*1280 | 2100*1600*1450 | 2100*1700*1600 | 2100*1700*1600 |
Air conditioning and heating heat exchanger unit
| For air conditioning and underfloor heating systems (10°C temperature difference) | Model number | LZ-450-K/D- | LZ-600-K/D- | LZ-800-K/D- | LZ-1000-K/D- | LZ-1200-K/D- | LZ-1500-K/D- | LZ-2000-K/D- | |
| Heat Load (kW) | 450 | 600 | 800 | 1000 | 1200 | 1500 | 2500 | ||
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 767.6 | 1023 | 1365 | 1706 | 2047 | 2559 | 3412 | |
| Steam pipeline | 65 | 80 | 80 | 100 | 100 | 100 | 125 | ||
| Condensate piping | 32 | 32 | 40 | 40 | 50 | 50 | 50 | ||
| Heat source: 95/70℃ high-temperature water | Traffic | 15.5 | 20.6 | 27.5 | 34.4 | 41.3 | 51.6 | 68.8 | |
| Takeover Specifications | 65 | 80 | 80 | 100 | 100 | 125 | 125 | ||
| Secondary side: Water 10/60℃ | Traffic | 38.7 | 51.6 | 68.9 | 86.1 | 103 | 129 | 172 | |
| Takeover Specifications | 100 | 100 | 125 | 125 | 150 | 150 | 200 | ||
| Overall dimensions | Length * Width * Height | 2100*1650*1280 | 2100*1650*1280 | 2300*1900*1450 | 2300*1900*1450 | 2450*2150*1660 | 2450*2150*1660 | 2650*2250*1850 | |
| For air conditioning and underfloor heating systems (10°C temperature difference) | Model number | LZ-3000-K/D- | LZ-4500-K/D- | LZ-6000-K/D- | LZ-10000-K/D- |
LZ-20000-K/D- |
LZ-30000-K/D- |
LZ-40000-K/D- |
LZ-50000-K/D- |
LZ-60000-K/D- |
|
| Heat Load (kW) | 3000 | 4500 | 6000 | 10000 | 20000 | 30000 | 40000 | 50000 | 60000 | ||
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 5117 | 7676 | 10230 | 17060 | 34120 | 51170 | 68230 | 85290 | 102300 | |
| Steam pipeline | 150 | 200 | 200 | 300 | 400 | 500 | 550 | 600 | 650 | ||
| Condensate piping | 65 | 80 | 100 | 100 | 150 | 200 | 250 | 250 | 300 | ||
| Heat source: 95/70℃ high-temperature water | Traffic | 103 | 154 | 206 | 343.9 | 687.8 | 1032 | 1376 | 1719 | 2063 | |
| Takeover Specifications | 150 | 200 | 200 | 250 | 350 | 400 | 500 | 500 | 600 | ||
| Secondary side: Water 10/60℃ | Traffic | 258 | 387 | 516 | 862.6 | 1725 | 2588 | 3450 | 4313 | 5176 | |
| Takeover Specifications | 250 | 250 | 300 | 400 | 500 | 650 | 700 | 800 | 900 | ||
| Overall dimensions | Length * Width * Height | 2850*2350*1850 | 3300*2350*2080 | 3500*2350*2080 | Customization | Customization | Customization | Customization | Customization | Customization | |
| For heating systems (25°C temperature difference) | Model number | LZ-450-N - | LZ-600-K/D- | LZ-800-K/D- | LZ-1000-K/D- | LZ-1200-K/D- | LZ-1500-K/D- | LZ-2000-K/D- | |
| Heat Load (kW) | 450 | 600 | 800 | 1000 | 1200 | 1500 | 2500 | ||
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 767.6 | 1023 | 1365 | 1706 | 2047 | 2559 | 3412 | |
| Steam pipeline | 65 | 80 | 80 | 100 | 100 | 100 | 125 | ||
| Condensate piping | 32 | 32 | 40 | 40 | 50 | 50 | 50 | ||
| Heat source: 120/80℃ high-temperature water | Traffic | 9.7 | 12.9 | 17.2 | 21.5 | 25.8 | 32.2 | 43 | |
| Takeover Specifications | 50 | 65 | 65 | 80 | 80 | 100 | 100 | ||
| Secondary side: Water 70/95℃ | Traffic | 15.4 | 20.6 | 27.5 | 34.4 | 41.3 | 51.6 | 68.8 | |
| Takeover Specifications | 65 | 80 | 80 | 100 | 100 | 125 | 125 | ||
| Overall dimensions | Length * Width * Height | 2100*1600*1240 | 2200*1750*1280 | 2200*1750*1280 | 2350*1950*1280 | 2350*1950*1450 | 2450*1950*1450 | 2650*2100*1660 | |
| For heating systems (25°C temperature difference) | Model number | LZ-3000-K/D- | LZ-4500-K/D- | LZ-6000-K/D- | LZ-10000-K/D- |
LZ20000K/D- |
LZ-30000-K/D- |
LZ-40000-K/D- |
LZ-50000-K/D- |
LZ-60000-K/D- |
|
| Heat Load (kW) | 3000 | 4500 | 6000 | 10000 | 20000 | 30000 | 40000 | 50000 | 60000 | ||
| Heat source: saturated steam at 4 barg | Flow rate (KG/H) | 5117 | 7676 | 10230 | 17060 | 34120 | 51170 | 68230 | 85290 | 102300 | |
| Steam pipeline | 150 | 200 | 200 | 300 | 400 | 500 | 550 | 600 | 650 | ||
| Condensate piping | 65 | 80 | 100 | 100 | 150 | 200 | 250 | 250 | 300 | ||
| Heat source: 120/80℃ high-temperature water | Traffic | 64.5 | 96.7 | 129 | 213.8 | 427.6 | 641.3 | 855.1 | 1069 | 1283 | |
| Takeover Specifications | 125 | 150 | 150 | 200 | 300 | 350 | 400 | 450 | 450 | ||
| Secondary side: Water 70/95℃ | Traffic | 103 | 154 | 206 | 343.9 | 687.8 | 1032 | 1376 | 1719 | 2063 | |
| Takeover Specifications | 150 | 200 | 200 | 250 | 350 | 400 | 450 | 500 | 550 | ||
| Overall dimensions | Length * Width * Height | 2850*2350*1660 | 3200*2350*1850 | 3200*2350*1850 | Customization | Customization | Customization | Customization | Customization | Customization | |
Water, water-heat exchanger unit
Heat source for the heating unit
Non-standard units can prioritize using high-temperature wastewater for heat exchange, such as high-temperature steam condensate, with any shortfall supplemented by steam heating. This approach both reduces steam costs and saves on expenses associated with cooling and discharging wastewater.
Unit Control Instructions
The control system collects signals from the heat exchange unit, including primary and secondary side temperatures, pressures, differential pressure across the dirt separator, outdoor temperature, flow rates, and the manual/automatic and operating/fault statuses of the circulating and make-up pumps, and is capable of transmitting these
These signals are uploaded to the monitoring center via a remote terminal control system, enabling remote control. The controlled parameters include: secondary-side supply water temperature, pressure, and supply/return pressure differential.
Commonly Used Control Strategies
(1) The heat exchange unit features climate compensation and horizontal manifold water supply functionality.
The application programmable controller automatically sets the primary-side supply water temperature based on changes in outdoor temperature and the local heat load curve, and can also set a compensation value as required. The measured value of the secondary-side supply water temperature is compared with the setpoint,
Through PID control, the controller output signal adjusts the electric valve to regulate temperature.
(2) Automatic water replenishment
A pressure sensor installed on the secondary-side return pipe measures the pressure signal; after comparison with the setpoint, it outputs control commands to start or stop the make-up water pump or to adjust its speed via frequency conversion, thereby maintaining constant-pressure makeup.
(3) Automatic pressure relief function
The unit can select the hot water expansion overpressure within the Jin Xin buffer system of the pressure expansion tank.
Pressure relief can also be achieved using a waterproof solenoid valve;
To ensure absolute safety, both methods are equipped with safety valves.
(4) Secondary-side supply with return‑water differential pressure control: The return system requires a differential pressure bypass valve, typically installed between the distribution manifold and the collection manifold, or alternatively integrated into the heat exchange unit. Purpose: When the load decreases, the return pressure drops, causing the circulating pump to operate at a low flow rate. Frequent load fluctuations would lead to continuous changes in the pump’s operating condition, shortening its service life. In such cases, the differential pressure bypass valve, connected in parallel with the load, opens to maintain adequate water circulation throughout the system. On the other hand, without controlling the supply–return differential pressure, water tends to return preferentially from the terminal users; when these terminal users are operating at high loads, they may not receive sufficient flow.
Even with a differential pressure bypass valve installed, most users still opt for a variable-frequency circulation pump to enhance system stability. The differential pressure setpoint can be configured on the local controller or remotely.
(5) Power-off protection function
When a sudden power outage occurs, the motorized valve on the primary side automatically shuts off the heat source (e.g., steam) to prevent overheating or even vaporization on the secondary side, which could damage the heat exchanger and piping. The controller and variable frequency drive automatically reset, restoring all set parameters and
The operating parameters remain as they were before the power was cut.
(6) Power-On Self-Test Function
The secondary return water pressure is equipped with a preset over‑pressure protection threshold. When the secondary side pressure fails to reach this set value, the circulating pump cannot be started; only the make‑up water pump may be activated to replenish water. The circulating pump can be started only after the pressure has reached the set value for heat exchange.
After power is supplied to the unit, it performs a self-check and sequentially starts each module.
(7) Undervoltage Protection
When the secondary-side return water pressure falls below the set value, the circulating pump automatically stops running.
(8) Over-temperature protection
When the primary-side heat source temperature exceeds 180 degrees, the electric valve automatically closes and an alarm signal is triggered.
(9) Overpressure Protection
When the secondary water supply pressure exceeds the set value, in addition to automatic pressure relief, the primary-side electric valve is also closed.
(10) Monitor the water tank level
When the water tank level falls below the ultra-low limit, the make-up water pump stops and an alarm signal is issued.
(11) Time Control Program
It can schedule power on/off, features an energy-saving mode, and allows for time-of-day heating schedules on a daily, weekly, or monthly basis.